Features
· Primary injection up to 750A
· 2.8V output (750ADM), 4V output (750ADM-H)
· 16V 40A output for secondary injection
· True RMS digital metering
· Memory ammeter
· Multi-function timing system
· Large back-lit liquid crystal display
· Thermal and over-current protection
· Automatic switch-off at end of test
· Compact and portable
· Automatic mains voltage selection

The 750ADM and 750ADM-H are compact, rugged primarycurrent injection systems with a 750A output capability. The 750ADM has a maximum no load output voltage of 3.5V andthe 750ADM-H has a maximum voltage of 5V. The units are ideally suited to all low power primary injection tasks requiring up to 750A for short periods.