PT30-10 high voltage dc test sets
The PT18-10 and PT30-10 high voltage dc test sets are designed to perform
tests on installed cable and jointing systems. The units have a variable
output voltage with a maximum or ±18kVdc (PT18-10) or ±30kVdc (PT30-10).
Both units have a maximum charging capability of 10mA. A zero-volt interlock
is fitted that prevents the output being switched on unless the output
control is at zero.
The units include an automatic load discharge system that discharges the
cable under test when the output is switched off or a breakdown occurs. The
internal dumping system can discharge a maximum of 2.5kJ on each output,
corresponding to 10mF at 18kV or 4mF at 30kV. In the event of a test object
failure, the overload circuit will automatically switch off the output
voltage and earth the output via the internal discharge circuit. A manual
discharge probe is also supplied as standard with both units, allowing
higher load capacitances to be safely discharged.
The output voltage is metered by two large, linear, analogue instruments
marked 0-20kV (PT18-10) or 0-30kV (PT30-10). Test object current is metered
by two further analogue instruments with 0-10 scale marking. The meters read
0-10mA directly, or 0- 1mA when the ¸10 push button is operated.
The HV output from the unit uses a high quality plug and socket system,
allowing for easy cable replacement.
Features
-
±18kVdc output voltage (PT18-10) ±30kVdc output voltage (PT30-10)
-
10mA output capability
-
Both voltage and current metered on HV outputs
-
Automatic earth system for dumping capacitive loads
-
HV output plug & socket system
-
Key operated supply switch to prevent unauthorised operation
-
Zero-volt interlock
-
Visual indication of test piece failure
Click
to enlarge specifications
|